range | TeSys | |
---|---|---|
product name | TeSys F | |
product or component type | Contactor | |
device short name | LC1F | |
contactor application | Motor control Resistive load | |
utilisation category | AC-3 AC-4 AC-1 | |
poles description | 3P | |
power pole contact composition | 3 NO | |
[Ue] rated operational voltage | <= 460 V DC <= 690 V AC 50/60 Hz | |
[Ie] rated operational current | 275 A (at <40 °C) at <= 440 V AC-1 185 A (at <55 °C) at <= 440 V AC-3 | |
motor power kW | 90 kW at 380...400 V AC 50/60 Hz (AC-3) 100 kW at 415 V AC 50/60 Hz (AC-3) 100 kW at 440 V AC 50/60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660...690 V AC 50/60 Hz (AC-3) 55 kW at 220...230 V AC 50/60 Hz (AC-3) 33 kW at 400 V AC 50/60 Hz (AC-4) | |
[Uc] control circuit voltage | 220 V AC 40...400 Hz |