Description

Main
range of productAltivar 212

product or component typeVariable speed drive

device short nameATV212

product destinationAsynchronous motors

product specific applicationPumps and fans in HVAC

assembly styleWith heat sink

network number of phases3 phases

motor power kW37 kW

motor power hp50 hp

[Us] rated supply voltage380...480 V - 15...10 %

supply voltage limits323…528 V

supply frequency50...60 Hz - 5...5 %

EMC filterClass C2 EMC filter integrated

line current68.9 A at 380 V
54.4 A at 480 V

Complementary
apparent power52 kVA at 380 V

prospective line Isc22 kA

continuous output current79 A at 380 V
79 A at 460 V

maximum transient current86.9 A for 60 s

speed drive output frequency0.5…200 Hz

nominal switching frequency8 kHz

switching frequency6...16 kHz adjustable
8...16 kHz with derating factor

speed range1…10

speed accuracy+/- 10 % of nominal slip 0.2 Tn to Tn

torque accuracy+/- 15 %

transient overtorque120 % of nominal motor torque +/- 10 % for 60 s

asynchronous motor control profileVoltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, 5 points
Voltage/frequency ratio - Energy Saving, quadratic U/f

regulation loopAdjustable PI regulator

motor slip compensationNot available in voltage/frequency ratio motor control
Adjustable
Automatic whatever the load

local signalling1 LED (red)DC bus energized:

output voltage<= power supply voltage

isolationElectrical between power and control

type of cableWithout mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC

electrical connectionVIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 50 mm² / AWG 1/0

tightening torque0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
24 N.m, 212 lb.in (L1/R, L2/S, L3/T)

supplyInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection

analogue input number2

analogue input typeVIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits

sampling duration2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog

response timeFM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)

accuracy+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C

linearity errorVIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output

analogue output number1

analogue output typeFM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits

discrete output number2

discrete output typeConfigurable relay logic: (FLA, FLC) NO - 100000 cycles
Configurable relay logic: (FLB, FLC) NC - 100000 cycles
Configurable relay logic: (RY, RC) NO - 100000 cycles

minimum switching current3 mA at 24 V DC for configurable relay logic

maximum switching current5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)

discrete input typeF programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm

discrete input logicPositive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)

acceleration and deceleration rampsLinear adjustable separately from 0.01 to 3200 s
Automatic based on the load

braking to standstillBy DC injection

protection typeOverheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor

dielectric strength3535 V DC between earth and power terminals
5092 V DC between control and power terminals

insulation resistance>= 1 mOhm 500 V DC for 1 minute

frequency resolutionDisplay unit: 0.1 Hz
Analog input: 0.024/50 Hz

communication port protocolLonWorks
Modbus
APOGEE FLN
METASYS N2
BACnet

connector type1 open style
1 RJ45

physical interface2-wire RS 485

transmission frameRTU

transmission rate9600 bps or 19200 bps

data format8 bits, 1 stop, odd even or no configurable parity

type of polarizationNo impedance

number of addresses1…247

communication serviceRead holding registers (03) 2 words maximum
Monitoring inhibitable
Write single register (06)
Write multiple registers (16) 2 words maximum
Read device identification (43)
Time out setting from 0.1 to 100 s

option cardCommunication card for LonWorks

operating positionVertical +/- 10 degree

width284 mm

height880 mm

depth343 mm

functionalityMid

specific applicationHVAC

IP degree of protectionIP55

Environment
electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

pollution degree3 conforming to IEC 61800-5-1

IP degree of protectionIP55 conforming to EN/IEC 61800-5-1
IP55 conforming to EN/IEC 60529

vibration resistance1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8

shock resistance15 gn for 11 ms conforming to IEC 60068-2-27

environmental characteristicClasses 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3

noise level64 dB conforming to 86/188/EEC

operating altitude1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without derating

relative humidity5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3

ambient air temperature for operation-10…40 °C (without derating)
40…50 °C (with derating factor)

ambient air temperature for storage-25…70 °C

standardsEN 61800-3
IEC 61800-5-1
EN 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C1
IEC 61800-3
EN 61800-3 environments 1 category C2
EN 55011 class A group 1
EN 61800-3 environments 1 category C1
EN 61800-3 category C2
IEC 61800-3 environments 1 category C3
IEC 61800-3 category C3
IEC 61800-3 category C2
IEC 61800-3 environments 1 category C2
EN 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
EN 61800-3 category C3
EN 61800-3 environments 2 category C3
EN 61800-3 environments 2 category C1
EN 61800-5-1
IEC 61800-3 environments 1 category C1

product certificationsNOM 117
UL
C-Tick
CSA

markingCE

Packing Units
Unit Type of Package 1PCE

Number of Units in Package 11

Package 1 Weight45.5 kg

Package 1 Height47 cm

Package 1 width50 cm

Package 1 Length120 cm

0
0
64