Description

Specifications

Hide

Range of product

  • TeSys D
  • TeSys F

Range

TeSys

Product or component type

time delay auxiliary contact block

Pole contact composition

1 NO + 1 NC

Shielding continuity terminal

without

Connections - terminals

  • screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
  • screw clamp terminals 1 cable(s) 1-2.5 mm²flexible without cable end
  • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
  • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible without cable end
  • screw clamp terminals 1 cable(s) 1-2.5 mm²solid with cable end
  • screw clamp terminals 1 cable(s) 1-2.5 mm²solid without cable end
  • screw clamp terminals 2 cable(s) 1-2.5 mm²solid with cable end
  • screw clamp terminals 2 cable(s) 1-2.5 mm²solid without cable end

Mounting location

front

[Ui] rated insulation voltage

  • 600 V - certifications UL
  • 690 V conforming to IEC 60947-5-1
  • 600 V - certifications CSA

[Ue] rated operational voltage

690 V AC 25...400 Hz

[Ith] conventional free air thermal current

10 A (at 60 °C)

Irms rated making capacity

  • 140 A at <= 690 V AC conforming to IEC 60947-5-1
  • 250 A at <= 690 V DC conforming to IEC 60947-5-1

Permissible short-time rating

  • 100 A 60 °C 1 s
  • 120 A 60 °C 500 ms
  • 140 A 60 °C 100 ms

Protection type

gG fuse 10 A

Associated fuse rating

10 A gG conforming to IEC 60947-5-1

Mechanical durability

5 Mcycles

Minimum switching current

5 mA

Minimum switching voltage

17 V

Non-overlap time

  • 1.5 ms on de-energisation no overlap between NC and NO contact
  • 1.5 ms on energisation no overlap between NC and NO contact

Timer type

on delay

Time delay range

0.1...30 s

Insulation resistance

> 10 MOhm

Environmental characteristic

normal environment

Standards

  • EN 60947-5-1
  • NF C 63-140
  • IEC 60947-5-1
  • VDE 0660
  • BS 4794

Product certifications

  • CSA
  • UL

IP degree of protection

IP2x conforming to VDE 0106

Protective treatment

TH conforming to IEC 60068

Ambient air temperature for operation

-5-60 °C

Ambient air temperature for storage

-60-80 °C

Operating altitude

3000 m without

Sustainable offer status

Green Premium product

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP110702EN

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

0
0
19