range | TeSys | |
---|---|---|
product name | TeSys LRK | |
product or component type | Differential thermal overload relay | |
device short name | LR2K | |
relay application | Motor protection | |
product compatibility | LC7K LP1K LC1K LP4K | |
network type | DC AC | |
thermal overload class | Class 10A conforming to IEC 60947-4-1 | |
thermal protection adjustment range | 8…11.5 A | |
[Ui] rated insulation voltage | Power circuit: 690 V conforming to BS 4941 Power circuit: 690 V conforming to IEC 60947 Power circuit: 750 V conforming to VDE 0110 group C Power circuit: 600 V conforming to CSA C22.2 No 14 |
network frequency | <= 400 Hz | |
---|---|---|
mounting support | Under contactor Plate, with specific accessories Rail, with specific accessories | |
auxiliary contact composition | 1 NO + 1 NC | |
[Ith] conventional free air thermal current | 6 A for signalling circuit | |
[Ue] rated operational voltage | <= 690 V for power circuit 690 V AC AC-15 for signalling circuit 250 V DC DC-13 for signalling circuit | |
associated fuse rating | 6 A gG for signalling circuit conforming to VDE 0660 6 A gG for signalling circuit conforming to IEC 60947 | |
[Uimp] rated impulse withstand voltage | 6 kV | |
power dissipation per pole | 2 W | |
phase failure sensitivity | Yes conforming to IEC 60947-4-1 | |
local signalling | Trip indicator (yellow) | |
control type | Red push-button: trip test function Blue push-button: stop and manual reset selector switch: manual or automatic reset | |
connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid Screw clamp terminals 2 cable(s) 1.5…4 mm²solid Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end | |
tightening torque | 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm | |
height | 58 mm | |
width | 45 mm | |
depth | 65 mm | |
net weight | 0.145 kg |
standards | IEC 60947 VDE 0660 BS 4941 NF C 63-650 | |
---|---|---|
product certifications | UL CSA | |
protective treatment | TC conforming to IEC 60068 TC conforming to DIN 50016 | |
IP degree of protection | IP2x conforming to IEC 60529 | |
ambient air temperature for operation | -20…55 °C without derating conforming to IEC 60947 -30…60 °C with derating conforming to IEC 60947 | |
ambient air temperature for storage | -40…70 °C | |
operating altitude | 2000 m without derating | |
fire resistance | 850 °C conforming to IEC 60695-2-1 | |
flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 | |
mechanical robustness | Shocks NO contact: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks NC contact: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations NO contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations NC contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
Unit Type of Package 1 | PCE | |
---|---|---|
Number of Units in Package 1 | 1 | |
Package 1 Weight | 159 g | |
Package 1 Height | 4.8 cm | |
Package 1 width | 7.2 cm | |
Package 1 Length | 8.5 cm | |
Unit Type of Package 2 | S02 | |
Number of Units in Package 2 | 41 | |
Package 2 Weight | 6.852 kg | |
Package 2 Height | 15 cm | |
Package 2 width | 30 cm | |
Package 2 Length | 40 cm |