range | VarPlus | |
---|---|---|
device short name | DR | |
product or component type | Detuned reactor | |
network frequency | 50 Hz | |
reactive power rating | 12.5 kvar for 400 V AC 50 Hz | |
network rated voltage | 400 V AC 50 Hz | |
tuning order | 3.8 - 190 Hz - 7 % - 50 Hz |
power losses (max) | 150 W | |
---|---|---|
value of inductance | 2.987 mH | |
inductance tolerance | - 5 % to 5 % per phase | |
fundamental current rating | 18 A | |
RMS current rating | 19.5 A | |
electrical insulation class | Class H | |
[Ui] rated insulation voltage | 1.1 kV | |
dielectric test voltage | 4 kV 50 Hz 1 minute | |
[Imp] maximum permanent current | 1.2 x I1 | |
harmonic current spectrum | 3.7 % x I3 38.2 % x I5 13.6 % x I7 4.9 % x I11 | |
dynamic withstand current | 2.2 x Isc | |
[Ith] conventional free air thermal current | 2 A at 250 V AC 50 Hz | |
type of installation | Indoor installation | |
type of cooling | Forced convection | |
connections - terminals | Pad terminal | |
fixing center | 200 x 125 mm | |
height | 220 mm | |
width | 240 mm | |
depth | 160 mm | |
net weight | 10 kg |
standards | IEC 60068 | |
---|---|---|
IP degree of protection | IP00 | |
operating altitude | <= 2000 m | |
ambient air temperature for operation | 0…55 °C at <= 1000 m 0…50 °C at > 1000...2000 m | |
average ambient air temperature for operation | 50 °C at <= 1000 m (average over 24 hours) 40 °C at <= 1000 m (average over 1 year) 45 °C at > 1000...2000 m (average over 24 hours) 35 °C at > 1000...2000 m (average over 1 year) | |
climatic withstand | Relative humidity: 20...80 % Salt mist (400 V/50 Hz) : 250 hours |
Unit Type of Package 1 | PCE | |
---|---|---|
Number of Units in Package 1 | 1 | |
Package 1 Weight | 10.05 kg | |
Package 1 Height | 24.5 cm | |
Package 1 width | 29 cm | |
Package 1 Length | 30.5 cm |