Description

Main
rangeTeSys

product nameTeSys VARIO

device short nameVCF

product or component typeEmergency stop switch disconnector

performance levelHigh performance

poles description3P

contacts type and composition3 NO

network typeDC
AC

control typeRotary handle

rotary handle mounting styleDirect

handle colourRed

handle front plate colourYellow

suitability for isolationYes

Complementary
rotary handle padlocking1 to 3 padlocks 4…8 mm

marking0 - 1

mounting supportHandle: door
Switch: door

fixing modeBy 4 screws for handle

[Ue] rated operational voltage690 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage8 kV

[Ith] conventional free air thermal current80 A

[Ithe] conventional enclosed thermal current63 A

[Ie] rated operational current57 A AC-23 Ue: 400 V

rated operational power in W18.5 kW at 690 V (AC-3)
15 kW at 230...240 V (AC-3)
22 kW at 400...415 V (AC-3)
30 kW at 500 V (AC-3)
30 kW at 690 V (AC-23A)
37 kW at 500 V (AC-23A)
18.5 kW at 230...240 V (AC-23A)
30 kW at 400...415 V (AC-23A)

intermittent duty class30

Making capacity ( I Rms)800 A at 400 V AC-21A
800 A at 400 V AC-22A
800 A at 400 V AC-23A

[Icm] rated short-circuit making capacity2.1 kA at 400 V at Ipeak

[Icw] rated short-time withstand Rms current960 A at 400 V duration: 1 s

rated conditional short-circuit current10 kA at 400 V - associated fuse 80 A aM
10 kA at 400 V - associated fuse 80 A gG

breaking capacity640 A at 400 V (AC-21A)
640 A at 400 V (AC-22A)
640 A at 400 V (AC-23A)

device compositionSwitch
Handle

mechanical durability30000 cycles

electrical durability30000 cycles AC-21
30000 cycles DC-1...5

connections - terminalsPower circuit: screw clamp terminals25 mm² - solid
Power circuit: screw clamp terminals16 mm² - flexible - with cable end

tightening torquePower circuit: 4 N.m - on screw clamp terminals

handle front plate dimension60 x 60 mm

height83 mm

width60 mm

net weight0.56 kg

0
0
30