range | TeSys | |
---|---|---|
product name | TeSys GV2 | |
device short name | GV2P | |
device application | Motor | |
trip unit technology | Thermal-magnetic |
poles description | 3P | |
---|---|---|
network type | AC | |
utilisation category | AC-3 IEC 60947-4-1 Category A IEC 60947-2 | |
network frequency | 50/60 Hz IEC 60947-4-1 | |
fixing mode | 35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws) | |
operating position | Any position | |
motor power kW | 9 kW 400/415 V AC 50/60 Hz 11 kW 500 V AC 50/60 Hz 18.5 kW 690 V AC 50/60 Hz | |
breaking capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 | |
[Ics] rated service short-circuit breaking capacity | 100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 75 % 500 V AC 50/60 Hz IEC 60947-2 50 % 400/415 V AC 50/60 Hz IEC 60947-2 75 % 440 V AC 50/60 Hz IEC 60947-2 | |
control type | Rotary knob | |
Line Rated Current | 23 A | |
thermal protection adjustment range | 17…23 A | |
magnetic tripping current | 327 A | |
[Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 | |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 | |
[Ith] conventional free air thermal current | 23 A IEC 60947-4-1 | |
[Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 | |
power dissipation per pole | 2.5 W | |
mechanical durability | 100000 cycles | |
electrical durability | 100000 cycles AC-3 440 V | |
maximum operating rate | 25 cyc/h | |
rated duty | Continuous IEC 60947-4-1 | |
connections - terminals | screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) solid screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible with cable end | |
tightening torque | 15.05 lbf.in (1.7 N.m) screw clamp terminals | |
suitability for isolation | Yes IEC 60947-1 | |
phase failure sensitivity | Yes IEC 60947-4-1 | |
Maximum Height | 3.50 in (89 mm) | |
Maximum Width | 1.77 in (45 mm) | |
Maximum Depth | 3.82 in (97 mm) |
standards | EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 | |
---|---|---|
product certifications | IECEE CB Scheme UL CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL RINA | |
protective treatment | TH | |
IP degree of protection | IP20 IEC 60529 | |
IK degree of protection | IK04 | |
ambient air temperature for operation | -4…140 °F (-20…60 °C) | |
ambient air temperature for storage | -40…176 °F (-40…80 °C) | |
fire resistance | 1760 °F (960 °C) IEC 60695-2-1 | |
operating altitude | 6561.68 ft (2000 m) |
Category | 22367 - MANUAL STR PROTECTOR - GV2 | |
---|---|---|
Discount Schedule | I11 | |
GTIN | 00785901832966 | |
Nbr. of units in pkg. | 1 | |
Package weight(Lbs) | 0.4 lb(US) (0.18 kg) | |
Returnability | Yes | |
Country of origin | TH |
Unit Type of Package 1 | PCE | |
---|---|---|
Package 1 Height | 1.89 in (4.8 cm) | |
Package 1 width | 3.66 in (9.3 cm) | |
Package 1 Length | 3.94 in (10 cm) | |
Unit Type of Package 2 | S02 | |
Number of Units in Package 2 | 20 | |
Package 2 Weight | 15.64 lb(US) (7.094 kg) | |
Package 2 Height | 5.91 in (15 cm) | |
Package 2 width | 11.81 in (30 cm) | |
Package 2 Length | 15.75 in (40 cm) | |
Unit Type of Package 3 | P06 | |
Number of Units in Package 3 | 320 | |
Package 3 Weight | 273.24 lb(US) (123.94 kg) | |
Package 3 Height | 31.50 in (80 cm) | |
Package 3 width | 31.50 in (80 cm) | |
Package 3 Length | 23.62 in (60 cm) |