Description

Main
device applicationMotor

rangeActi 9

product nameActi 9 iC60

product or component typeMiniature circuit-breaker

device short nameIC60L

poles description2P

number of protected poles2

[In] rated current10 A

network typeAC

trip unit technologyMagnetic

curve codeMA

breaking capacity15 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
40 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2

utilisation categoryCategory A conforming to EN 60947-2
Category A conforming to IEC 60947-2

suitability for isolationYes conforming to EN 60947-2
Yes conforming to IEC 60947-2

standardsEN 60947-2
IEC 60947-2

Complementary
network frequency50/60 Hz

magnetic tripping limit12 x In +/- 20 %

[Ics] rated service breaking capacity10 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
10 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
20 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
20 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz

limitation class3 conforming to EN 60898-1
3 conforming to IEC 60898-1

[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2

contact position indicatorYes

control typeToggle

local signallingTrip indicator

mounting modeFixed

mounting supportDIN rail

comb busbar and distribution block compatibilityTop or bottom: YES

9 mm pitches4

height85 mm

width36 mm

depth78.5 mm

net weight0.25 kg

colourWhite

mechanical durability20000 cycles

electrical durability10000 cycles

connections - terminalsSingle terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible

wire stripping length14 mm for top or bottom connection

tightening torque2 N.m top or bottom

earth-leakage protectionSeparate block

0
0