range | TeSys | |
---|---|---|
product name | TeSys LRF | |
device short name | LR9F | |
product or component type | Electronic thermal overload relay | |
relay application | Motor protection | |
product compatibility | LC1F115...LC1F185 | |
network type | AC | |
thermal overload class | Class 20 conforming to IEC 60947-4 | |
thermal protection adjustment range | 60…100 A | |
signalling function | Pre-alarm indicator |
network frequency | 50/60 Hz | |
---|---|---|
supply voltage limits | 17…32 V | |
mounting support | Direct on contactor Plate | |
tripping threshold | 1.12 +/- 0.06 In tripping conforming to IEC 60947-4-1 | |
surge withstand | 4 kV conforming to IEC 61000-4-5 | |
contacts type and composition | 1 NO + 1 NC | |
[Ith] conventional free air thermal current | 5 A for control circuit | |
[Ue] rated operational voltage | 1000 V AC 50/60 Hz for power circuit conforming to VDE 0110 group C | |
[Ui] rated insulation voltage | Power circuit: 1000 V AC conforming to IEC 60947-4 | |
[Uimp] rated impulse withstand voltage | IEC 60947-1 8 kV | |
phase failure sensitivity | Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1 | |
reset | Manual reset | |
control type | Dial white full-load current adjustment Test button red Push-button red reset Push-button stop | |
local signalling | Trip indicator | |
temperature compensation | -20…70 °C | |
current consumption | <= 5 mA no-load | |
switching capacity for alarm | 0...150 mA | |
maximum voltage drop | <2.5 V closed state | |
connections - terminals | Control circuit: screw clamp terminals 1 cable 0.75…2.5 mm² - cable stiffness: flexible - with cable end Control circuit: screw clamp terminals 1 cable 0.75…2.5 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 cable 0.75…4 mm² - cable stiffness: flexible - without cable end Control circuit: screw clamp terminals 2 cable 1…1.5 mm² - cable stiffness: flexible - with cable end Control circuit: screw clamp terminals 2 cable 1…2.5 mm² - cable stiffness: flexible - without cable end Control circuit: screw clamp terminals 2 cable 1 mm² - cable stiffness: solid Power circuit: lugs-ring terminals M8 | |
tightening torque | Control circuit: 1.2 N.m on screw clamp terminals Power circuit: 18 N.m on screw clamp terminals | |
height | 96 mm | |
width | 115 mm | |
depth | 123.5 mm | |
net weight | 0.9 kg |
standards | IEC 60947-4-1 IEC 60255-17 IEC 60255-8 EN 60947-4-1 VDE 0660 | |
---|---|---|
product certifications | UL CSA | |
protective treatment | TH | |
IP degree of protection | IP20 conforming to IEC 60529 | |
ambient air temperature for operation | -20…55 °C conforming to IEC 60255-8 | |
ambient air temperature for storage | -40…85 °C | |
operating altitude | <= 2000 m without derating | |
fire resistance | 850 °C conforming to IEC 60695-2-1 | |
mechanical robustness | Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7 Vibrations 5...300 Hz: 2 Gn conforming to IEC 60068-2-6 | |
dielectric strength | 6 kV 50 Hz conforming to IEC 255-5 | |
electromagnetic compatibility | Resistance to electrostatic discharge: 6 kV in indirect mode conforming to IEC 61000-4-2 Resistance to electrostatic discharge: 8 kV in air conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test: 10 V/m conforming to IEC 61000-4-3 Fast transients immunity test: 2 kV conforming to IEC 61000-4-4 |
Unit Type of Package 1 | PCE | |
---|---|---|
Number of Units in Package 1 | 1 | |
Package 1 Weight | 882 g | |
Package 1 Height | 13 cm | |
Package 1 width | 15.5 cm | |
Package 1 Length | 16 cm | |
Unit Type of Package 2 | S04 | |
Number of Units in Package 2 | 12 | |
Package 2 Weight | 11.309 kg | |
Package 2 Height | 30 cm | |
Package 2 width | 40 cm | |
Package 2 Length | 60 cm |