Description

Main
rangeActi 9

product nameDisbo iC60

product or component typeMiniature circuit-breaker

device short nameIC60N

poles description4P

number of protected poles4

[In] rated current63 A

network typeAC/DC

trip unit technologyThermal-magnetic

curve codeC

breaking capacity6 kA Icu at 100...133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2

utilisation categoryCategory A conforming to EN/IEC 60947-2

Complementary
network frequency50/60 Hz

[Ue] rated operational voltage440 V AC 50/60 Hz

magnetic tripping limit8 x In +/- 20 %

[Ics] rated service breaking capacity27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC

limitation class3 conforming to EN/IEC 60947-2

[Ui] rated insulation voltage500 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

contact position indicatorYes

control typeToggle

local signallingTrip indicator

mounting modeClip-on

mounting supportRail

9 mm pitches8

height85 mm

width72 mm

depth78.5 mm

net weight0.5 kg

colourWhite

mechanical durability20000 cycles

electrical durability10000 cycles

provision for padlockingPadlockable

connections - terminalsSingle terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible

wire stripping length14 mm for top or bottom connection

tightening torque3.5 N.m top or bottom

earth-leakage protectionSeparate block

0