range | TeSys | |
---|---|---|
product name | TeSys GV3 | |
device short name | GV3L | |
device application | Motor | |
poles description | 3P | |
network type | AC | |
utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 | |
network frequency | 50/60 Hz | |
breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz 50 kA Icu at 400/415 V AC 50/60 Hz | |
[Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz 100 % at 400/415 V AC 50/60 Hz 100 % at 440 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz | |
trip unit technology | Magnetic | |
magnetic tripping current | 700 A |
fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) | |
---|---|---|
operating position | Any position | |
motor power kW | 22 kW at 400/415 V AC 50/60 Hz 30 kW at 500 V AC 50/60 Hz 45 kW at 690 V AC 50/60 Hz | |
control type | Rotary knob | |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Uimp] rated impulse withstand voltage | IEC 60947-2 6 kV | |
mechanical durability | 50000 cycles | |
electrical durability | 50000 cycles for AC-3 at 415 V | |
maximum operating rate | 25 cyc/h | |
connections - terminals | EverLink BTR screw connectors 1 cable(s) 1…35 mm² solid EverLink BTR screw connectors 2 cable(s) 1…25 mm² solid EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible without cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible without cable end EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible with cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible with cable end | |
tightening torque | 5 N.m on EverLink BTR screw connectors for cable 25 mm² 8 N.m on EverLink BTR screw connectors for cable 35 mm² | |
mechanical robustness | Shocks: 15 Gn for 11 ms closed conforming to IEC 60068-2-27 Shocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27 Vibrations: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 | |
suitability for isolation | Yes conforming to IEC 60947-1 | |
height | 132 mm | |
width | 55 mm | |
depth | 136 mm | |
net weight | 0.96 kg |
standards | EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 | |
---|---|---|
product certifications | IECEE CB Scheme UL CSA CCC EAC ABS LROS (Lloyds register of shipping) DNV-GL BV | |
protective treatment | TH | |
IP degree of protection | IP20 conforming to IEC 60529 | |
IK degree of protection | IK09 | |
ambient air temperature for operation | -20…60 °C | |
ambient air temperature for storage | -40…80 °C | |
fire resistance | 960 °C conforming to IEC 60695-2-1 | |
operating altitude | 0...3000 m |
Unit Type of Package 1 | PCE | |
---|---|---|
Number of Units in Package 1 | 1 | |
Package 1 Weight | 1.001 kg | |
Package 1 Height | 6.5 cm | |
Package 1 width | 14.5 cm | |
Package 1 Length | 16 cm | |
Unit Type of Package 2 | P06 | |
Number of Units in Package 2 | 60 | |
Package 2 Weight | 73.06 kg | |
Package 2 Height | 80 cm | |
Package 2 width | 80 cm | |
Package 2 Length | 60 cm |