Description

Main
rangeTeSys

product nameTeSys VARIO

device short nameVCCF

product or component typeEmergency stop switch disconnector

performance levelHigh performance

poles description3P

contacts type and composition3 NO

network typeDC
AC

control typeRotary handle

rotary handle mounting styleExtended

handle colourRed

handle front plate colourYellow

suitability for isolationYes

Complementary
rotary handle padlocking1 to 3 padlocks 4…8 mm

marking0 - 1

mounting supportHandle: door
Switch: symmetrical rail
Switch: plate

fixing modeBy 4 screws for handle
By clips for switch
By screws for switch

[Ue] rated operational voltage690 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage8 kV

[Ith] conventional free air thermal current63 A

[Ithe] conventional enclosed thermal current50 A

[Ie] rated operational current41.5 A AC-23 Ue: 400 V

rated operational power in W11 kW at 230...240 V (AC-3)
22 kW at 500 V (AC-3)
22 kW at 690 V (AC-23A)
30 kW at 500 V (AC-23A)
18.5 kW at 400...415 V (AC-3)
18.5 kW at 690 V (AC-3)
15 kW at 230...240 V (AC-23A)
22 kW at 400...415 V (AC-23A)

intermittent duty class30

Making capacity ( I Rms)630 A at 400 V AC-21A
630 A at 400 V AC-22A
630 A at 400 V AC-23A

[Icm] rated short-circuit making capacity2.1 kA at 400 V at Ipeak

[Icw] rated short-time withstand Rms current756 A at 400 V duration: 1 s

rated conditional short-circuit current10 kA at 400 V - associated fuse 63 A aM
10 kA at 400 V - associated fuse 63 A gG

breaking capacity500 A at 400 V (AC-21A)
500 A at 400 V (AC-22A)
500 A at 400 V (AC-23A)

device compositionSwitch
Handle
Shaft extension

mechanical durability30000 cycles

electrical durability30000 cycles AC-21
30000 cycles DC-1...5

connections - terminalsPower circuit: screw clamp terminals25 mm² - solid
Power circuit: screw clamp terminals16 mm² - flexible - with cable end

tightening torquePower circuit: 4 N.m - on screw clamp terminals

handle front plate dimension60 x 60 mm

height83 mm

width60 mm

net weight0.44 kg

0
0
29