Description

• Timer type - OFF delay.

Environmental characteristics
Complementary characteristics
Main characteristics
Range of productTeSys D
TeSys F
Pole contact composition1NO+1NC
Connections - terminalssolid cable without cable end2 х 1...2,5 mm2 / 1 x 1...2,5 mm2
solid cable with cable end2 х 1...2,5 mm2 / 1 x 1...2,5 mm2
flexible cable without cable end2 х 1...2,5 mm2 / 1 x 1...2,5 mm2
гflexible cable with cable end2 х 1...2,5 mm2 / 1 x 1...2,5 mm2
Mounting locationfront
Rated insulation voltage UiCSA600V
IEC 60947-5-1690V
UL600V
Rated operational voltage Ue690V 25...400Hz
Conventional free air thermal current Ith10A at ≤ 60°C
Rated making capacity IrmsAC140A at U ≤ 690V
DC250A at U ≤ 690V
Permissible short-time rating140A at -5°C...+60°C 100ms
120A at -5°C...+60°C 500ms
100A at -5°C...+60°C 1s
Protection typeGG fuse ≤ 10A for Ue ≤ 690V
Mechanical durability5 000 000 cycles
Min switching current5mA
Min switching voltage17V
Timer typeOff delay
Time delay range10s...180s
Insulation resistance> 10MΩ
Product weight0,06 kg
Degree of protectionIP2x conforming to VDE 0106
Ambient air temperature for operation-5°C...+60°C
Ambient air temperature for storage-60°C...+80°C

0
0
17