Description

Main
rangeTeSys

product nameTeSys CAD

product or component typeControl relay

device short nameCAD

contactor applicationControl circuit

Complementary
utilisation categoryDC-13
AC-14
AC-15

pole contact composition3 NO + 2 NC

[Ue] rated operational voltage<= 690 V AC 25...400 Hz

control circuit typeAC at 50/60 Hz

[Uc] control circuit voltage220 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947

[Ith] conventional free air thermal current10 A (at 60 °C)

Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1

[Icw] rated short-time withstand current100 A - 1 s
120 A - 500 ms
140 A - 100 ms

associated fuse rating10 A gG conforming to IEC 60947-5-1

[Ui] rated insulation voltage600 V UL certified
600 V CSA certified
690 V conforming to IEC 60947-5-1

mounting supportPlate
Rail

connections - terminalsScrew clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end

tightening torque1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm

operating time12...22 ms coil energisation and NO closing
4...12 ms coil de-energisation and NO opening
4...19 ms coil energisation and NC opening
6...17 ms coil de-energisation and NC closing

mechanical durability30 Mcycles

maximum operating rate180 cyc/mn

inrush power in VA70 VA 50 Hz (at 20 °C)

hold-in power consumption in VA8 VA 50 Hz (at 20 °C)

minimum switching voltage17 V

minimum switching current5 mA

non-overlap time1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact

insulation resistance> 10 MOhm

mechanical robustnessShocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6

height77 mm

width45 mm

depth84 mm

net weight0.58 kg

0
0