Description

Main
range of productEasyPact

product or component typeCircuit breaker

device short nameEasypact EZC100N

circuit breaker nameEasypact EZC100N

device applicationDistribution

poles description3P

protected poles description3t

network typeDC
AC

network frequency50/60 Hz

[In] rated current100 A at 40 °C

[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

[Ue] rated operational voltage550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2

breaking capacity codeN

breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service breaking capacity5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

suitability for isolationYes conforming to IEC 60947-2

utilisation categoryCategory A

trip unit nameTM-D

trip unit technologyThermal-magnetic

trip unit rating30 A at 50 °C

protection typeOverload protection
Short-circuit protection

pollution degree3 conforming to IEC 60664-1
3 conforming to IEC 947-1

Complementary
control typeToggle

mounting modeFixed

mounting supportBackplate

upside connectionFront

downside connectionFront

mechanical durability8500 cycles

electrical durabilityCategory A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2

connection pitch25 mm

local signallingPositive contact indication

neutral protection settingWithout protection

earth-leakage protectionWithout

height130 mm

width75 mm

depth60 mm

0
0
60