range | Acti 9 | |
---|---|---|
product name | Acti 9 iID | |
product or component type | Residual current circuit breaker (RCCB) | |
device short name | IID | |
poles description | 2P | |
neutral position | Left | |
[In] rated current | 40 A | |
network type | AC | |
earth-leakage sensitivity | 30 mA | |
earth-leakage protection time delay | Instantaneous | |
earth-leakage protection class | Type AC |
device location in system | Outgoer | |
---|---|---|
network frequency | 50/60 Hz | |
[Ue] rated operational voltage | 220...240 V AC 50/60 Hz | |
residual current tripping technology | Voltage independent | |
rated breaking and making capacity | Idm 1500 A Im 1500 A | |
rated conditional short-circuit current | 10 kA | |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz | |
[Uimp] rated impulse withstand voltage | 6 kV | |
surge current | 250 A | |
contact position indicator | Yes | |
control type | Toggle | |
mounting mode | Clip-on | |
mounting support | DIN rail | |
9 mm pitches | 4 | |
height | 91 mm | |
width | 36 mm | |
depth | 73.5 mm | |
net weight | 0.21 kg | |
colour | White | |
mechanical durability | 20000 cycles | |
electrical durability | AC-1: 15000 cycles | |
locking options description | Padlocking device | |
connections - terminals | Single terminal top or bottom 1…35 mm² rigid Single terminal top or bottom 1…25 mm² flexible Single terminal top or bottom 1…25 mm² flexible with ferrule | |
wire stripping length | 14 mm for top or bottom connection | |
tightening torque | 3.5 N.m top or bottom |