Description

Main
rangeTeSys

product nameTeSys VARIO

device short nameVCF

product or component typeEnclosed emergency stop switch disconnector

performance levelHigh performance

poles description3P

control typeRotary handle

handle colourRed

handle front plate colourYellow

rotary handle padlocking1 to 3 padlocks 4…8 mm

Complementary
marking0 - 1

[Ue] rated operational voltage690 V AC

[Uimp] rated impulse withstand voltage8 kV

[Ithe] conventional enclosed thermal current50 A

[Ie] rated operational current41.5 A (AC-23A) at 400 V

rated operational power in W22 kW at 400 V (AC-23)
18.5 kW at 400 V (AC-3)

intermittent duty class30

Making capacity ( I rms)630 A at 400 V AC-21A
630 A at 400 V AC-22A
630 A at 400 V AC-23A

[Icm] rated short-circuit making capacity2.1 kA at 400 V at Ipeak

[Icw] rated short-time withstand Rms current756 A at 400 V duration: 1 s

rated conditional short-circuit current10 kA at 400 V - associated fuse 63 A aM
10 kA at 400 V - associated fuse 63 A gG

breaking capacity500 A at 400 V (AC-21A)
500 A at 400 V (AC-22A)
500 A at 400 V (AC-23A)

mechanical durability30000 cycles

electrical durability30000 cycles AC-21
30000 cycles DC-1...5

environmental characteristicStandard environment

suitability for isolationYes

connections - terminalsScrew clamp terminals16 mm² - flexible - with cable end
Screw clamp terminals25 mm² - solid

tightening torque4 N.m - on screw clamp terminals

fire resistance960 °C conforming to IEC 60595-2-1

handle front plate dimension60 x 60 mm

height180 mm

width157 mm

depth152 mm

net weight0.93 kg

0
0
23